‧AC‧S280RAP

280x280x88.9mm/11x3.5inch
1450 CFM
Sinwan Plastic Impeller Tubeaxial Fan
  Rated
Volt
Voltage
Range
Freq Input
Power
Ref.
Speed
Max.Airflow Max.Static Pressure Noise
Level
PQ UL
Model No VAC VAC Hz Watt

RPM

CFM m3/min Inch/H2O mm db(A)    
S280RAP-11-1** 115 100~120 50/60 181/286 2800/3200 1300/1450 36.8/41.1 1.25/1.1 31.75/27.94 75 2/1 £
S280RAP-11-2** 115 100~120 50/60 58/55 1500/1700 650/750 18.4/21.2 0.38/0.49 9.65/12.45 48 4/3 £
S280RAP-11-3** 115 100~120 50/60 32/37 1100/1000 465/450 13.2/12.7 0.16/0.11 4.06/2.79 35 6/5 £
S280RAP-22-1** 230 200~240 50/60 181/286 2800/3200 1300/1450 36.8/41.1 1.25/1.1 31.75/27.94 75 2/1 £
S280RAP-22-2** 230 200~240 50/60 58/55 1500/1700 650/750 18.4/21.2 0.38/0.49 9.65/12.45 48 4/3 £
S280RAP-22-3** 230 200~240 50/60 32/37 1100/1000 465/450 13.2/12.7 0.16/0.11 4.06/2.79 35 6/5 £
S280RAP-38-1** 380 380~420 50/60 90/140 2750/3000 1280/1360 36.2/38.5 1.2/1 30.48/25.4 75 2/1 £
S280RAP-44-1** 440 440~480 50/60 90/140 2750/3000 1280/1360 36.2/38.5 1.2/1 30.48/25.4 75 2/1 £
S280RAP-11/22-1**
dual voltage
115
230
100~120
200~240
50/60 181/286 2800/3200 1300/1450 36.8/41.1 1.25/1.1 31.75/27.94 75 2/1 £
  • ** = "WB" for wire lead type Ball bearing, or "TB" for terminal type Ball bearing
  • 100, 200, 240V or special voltages 12, 24, 28, 38, 42, 48, 380~440~480... 50/60Hz, & dual voltage version available on request.
  • Dual speed High/Medium 1/2, High/Low 1/3, Medium/Low 2/3, Low/extra Low 3/4 or triple speed 1/2/3 available on request.
  • Sinwan reserves the right to change data and improve electrical or mechanical design without notice, data tolerance +-10%
  •  
      Motor Type: Capacitor induction, inner rotor, 1-phase
      Burnout Protection: Thermal protector, auto cut-off, auto reset
      IP Protection: -
      Frame: Aluminum die cast, black color
      Impeller: 7 blades, glass fiber reinforced plastic, rated UL94V-0
      Bearing: Two ball bearings
      Rotation: CCW seen on rotor
      Connection: Wire leads, or push-in terminal flat pins
      Weight: 3,950g ( 8.7 Lbs)
      Dielectric Strength: Over 1 min. at 1,500 VAC, 0.5mA, 50/60 Hz
      Insulation Resistance: Over 100 MΩ at DC 500V
      Signal Output: Optional:alarm R/D, tachometer F/G
      Operating Temp: Ambient non-condensing -20~+70C
      Storage Temp: -40C~+100C (at 65%RH)
      Life Expectancy: L10 90K hours at 35C, 50K hours at 60C

     

    Metal Fan Guard
    G280-17U